DocumentCode :
1186432
Title :
Frequency Response of HV Test Transformers and the Associated Measurement Problems
Author :
Olivier, G. ; Bouchard, R.-P. ; Gervais, Y. ; Mukhedkar, D.
Author_Institution :
Concordia University
Issue :
1
fYear :
1980
Firstpage :
141
Lastpage :
146
Abstract :
This paper analyses the frequency response of HV test transformers. A single transformer or a cascade arrangement has been found to behave as a tuned filter with the peak frequencies between 150 Hz and 1 kHz well in the range of low-order harmonics. In consequence, the HV side presents distorted waveforms which cause more or less severe measurement errors, depending on the divider and the instrument used.
Keywords :
Capacitance; Capacitors; Circuit testing; Distortion measurement; Equivalent circuits; Frequency measurement; Frequency response; Instruments; Power harmonic filters; Transformers;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1980.319620
Filename :
4113779
Link To Document :