• DocumentCode
    1186604
  • Title

    Customer Service Direct From Transmission Lines

  • Author

    Wilde, R.L. ; Carr, J.

  • Author_Institution
    Saskatchewan Power Corporation
  • Issue
    1
  • fYear
    1980
  • Firstpage
    301
  • Lastpage
    306
  • Abstract
    This paper reports on the design, testing and commercial operation of apparatus to tap a 120/240V service directly from a 72kV transmission line. The installed apparatus consists of a capacitive voltage divider, a standard 14.4kV distribution transformer and auxiliary equipment for protection, regulation, resonance suppression etc. that together supply a 25kVA commercial load. Details are also given on variations of the basic circuit (use of inherent capacitance of transmission lines and inherent inductance of transformers) as well as on solutions to problems encountered during development (ferroresonance, regulation, flicker).
  • Keywords
    Capacitance; Customer service; Distributed parameter circuits; Electromagnetic coupling; Electrostatics; Impedance; Power transformer insulation; Power transmission lines; Transmission lines; Voltage transformers;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1980.319639
  • Filename
    4113799