DocumentCode :
1186621
Title :
Experience with Return Voltage Measurements for Assessing Insulation Conditions in Service Aged Transformers
Author :
Saha, Tapan Kumar ; Yao, Z. T.
Author_Institution :
University of Queensland
Volume :
22
Issue :
8
fYear :
2002
Firstpage :
70
Lastpage :
70
Abstract :
This paper describes the investigation of the insulation condition of a number of power and distribution type transformers of different manufacturing dates and with different operating histories. Return voltage measurements were conducted for these transformers. Effects of moisture and aging on the oilpaper insulation of these transformers were investigated, and results are presented. Moisture in oil samples at known temperature was measured for these transformers. Previously accelerated aging experiments were performed on paper-wrapped insulated conductors in different environments over a temperature range of 115 to 145 ??C. Results from the measurements on transformers are compared with those of the accelerated aged samples and are described.
Keywords :
Accelerated aging; Conductors; History; Moisture measurement; Oil insulation; Petroleum; Power transformer insulation; Pulp manufacturing; Temperature measurement; Voltage measurement; Power transformer; condition monitoring; dielectric measurement; insulation aging; insulation life; molecular weight; polarization; transformer insulation;
fLanguage :
English
Journal_Title :
Power Engineering Review, IEEE
Publisher :
ieee
ISSN :
0272-1724
Type :
jour
DOI :
10.1109/MPER.2002.4312523
Filename :
4312523
Link To Document :