DocumentCode
1186770
Title
The Response of Strain Bus to Short-Circuit Currents
Author
Craig, D.B. ; Ford, G.L.
Author_Institution
Ontario Hydro Research Division
Issue
2
fYear
1980
fDate
3/1/1980 12:00:00 AM
Firstpage
434
Lastpage
442
Abstract
Calculation methods for conductor tensions and displacements of strain bus under short-circuit conditions are compared with the results of full scale high current tests. The good agreement between theory and experiment has allowed use of these methods in designing new 100 kA substations and in uprating existing substations from 40 kA to 70 kA.
Keywords
Capacitive sensors; Circuit faults; Conductors; Fault currents; Hardware; Poles and towers; Structural beams; Substations; Testing; Timing;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1980.319678
Filename
4113821
Link To Document