Location of Partial Discharges in Power Transformers by Computation and Measurement of Capacitively Transmitted Voltage Pulses
Author
Källberg, Björn
Author_Institution
The Royal Institute of Technology
Issue
2
fYear
1980
fDate
3/1/1980 12:00:00 AM
Firstpage
589
Lastpage
596
Abstract
The voltage distribution in a power transformer after a partial discharge has occurred is calculated. The results are compared with voltages, measured at the terminals of the transformer. A partial discharge prediction curve, based on the calculated capacitive distribution is constructed, by which the location of partial discharges is improved. The location method is based on peak values or capacitive pulses measured at the terminals. Calculation of the complete winding resonances after a partial discharge is found not to be accurate enough for internal corona location purposes.
Keywords
Attenuation measurement; Capacitance; Fault location; Partial discharge measurement; Partial discharges; Power measurement; Power transformers; Pulse measurements; Pulse transformers; Transmission line measurements;