DocumentCode
1187023
Title
Automatic Phase Shift Method for Islanding Detection of Grid-Connected Photovoltaic Inverters
Author
Hung, Guo-Kiang ; Chang, Chih-Chang ; Chen, Chern-Lin
Author_Institution
National Taiwan University; AmbitMicrosystems Co.
Volume
22
Issue
9
fYear
2002
Firstpage
55
Lastpage
55
Abstract
The traditional frequency-shift methods for islanding detection of grid connected PV inverters (the active frequency-drift method and the slip mode frequency-shift method) become ineffective under certain paralleled RLC loads. The automatic phase-shift method is proposed in this paper to alleviate this problem. The method is based on the phase shift of the sinusoidal inverter output current. When the utility malfunctions, the phase-shift algorithm keeps the frequency of the inverter terminal voltage deviating until the protection circuit is triggered. Simulation and experiments are performed for verification.
Keywords
Coaxial cables; Dielectrics; Frequency; Fuzzy logic; Inverters; Load forecasting; Phase detection; Photovoltaic systems; Pyroelectricity; Solar power generation; Automatic phase shift; grid-connected photovoltaic inverters; inverters; islanding detection;
fLanguage
English
Journal_Title
Power Engineering Review, IEEE
Publisher
ieee
ISSN
0272-1724
Type
jour
DOI
10.1109/MPER.2002.4312568
Filename
4312568
Link To Document