    Clearance of Short-Circuits With Delayed Current Zeros in the Itaipu 550 kV-Substation

  • Author

    Kulicke, B. ; Schramm, H.H.

  • Author_Institution
    SIEMENS AG
  • Issue
    4
  • fYear
    1980
  • fDate
    7/1/1980 12:00:00 AM
  • Firstpage
    1406
  • Lastpage
    1414
  • Abstract
    The results of Kema-tests with short-circuit currents with delayed zeros carried out on a Siemens SF6 circuit-breaker have been transferred into a digital computer program and applied upon the conditions in the Itaipu 550 kV-substation for various cases of faults near the generators. The most critical condition occurs when the generators have been operating in the underexited state followed by a three-phase non-simultaneous fault at the entrance of a line. Theoretically there might be only one line in service and 5 generators feeding through one breaker. The circuit-braker under investigation will even clear this fault without necessitating any tripping delay.
  • Keywords
    Circuit faults; Circuit testing; Delay; Fault currents; Protection; Sulfur hexafluoride; Switchgear; Thermal stresses; Turbines; Voltage;