Clearance of Short-Circuits With Delayed Current Zeros in the Itaipu 550 kV-Substation
Author :
Kulicke, B. ; Schramm, H.H.
Author_Institution :
SIEMENS AG
Issue :
4
fYear :
1980
fDate :
7/1/1980 12:00:00 AM
Firstpage :
1406
Lastpage :
1414
Abstract :
The results of Kema-tests with short-circuit currents with delayed zeros carried out on a Siemens SF6 circuit-breaker have been transferred into a digital computer program and applied upon the conditions in the Itaipu 550 kV-substation for various cases of faults near the generators. The most critical condition occurs when the generators have been operating in the underexited state followed by a three-phase non-simultaneous fault at the entrance of a line. Theoretically there might be only one line in service and 5 generators feeding through one breaker. The circuit-braker under investigation will even clear this fault without necessitating any tripping delay.
Keywords :
Circuit faults; Circuit testing; Delay; Fault currents; Protection; Sulfur hexafluoride; Switchgear; Thermal stresses; Turbines; Voltage;