Title :
High-Inertia Drive Motors and Their Starting Characteristics
Author_Institution :
Sargent & Lundy
fDate :
7/1/1980 12:00:00 AM
Abstract :
The motor for a large reactor coolant pump failed while starting. The motor-application and the motor-failure are discussed in detail. A review of applications of motors for high-inertia drives shows that a motor designed and built to today´s industry-standards might be overstressed while experiencing abnormal starting conditions, even though its protection is in accord with accepted practice. The inter-relationship between motor characteristics and characteristics of various types of protection are discussed, briefly. Such protection is also discussed in a companion paper. [1] The review concludes that motor specifications and motor standards should be augmented.
Keywords :
Coolants; Costs; Drives; Inductors; Protection; Relays; Rotors; Senior members; Sensor phenomena and characterization; Stress;
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
DOI :
10.1109/TPAS.1980.319571