DocumentCode :
1188440
Title :
Shaft Torsional Stress Due to Asynchronous Faulty Synchronization
Author :
Mitsche, J.V. ; Rusche, P.A.
Author_Institution :
Consumers Power Company
Issue :
5
fYear :
1980
Firstpage :
1864
Lastpage :
1870
Abstract :
Oscillographic records of 345 kV breaker currents during an asynchronous faulty synchronization of a 955 MVA, 1800 r/min turbine-generator into a strong network are duplicated by a readily available digital program. The event is shown to have occurred with the machine running about 3% below synchronous speed and leading the grid by about 1200. Consequential shaft torsional oscillations are substantially greater in amplitude than those for a generator terminal fault. Furthermore, it is shown that for an asynchronous faulty synchronization, the character of the torsional oscillations will greatly increase the fatigue life expenditure. Rain flow cycle counts evaluated against manufacturer provided S/N curves show that the machine suffered moderately severe fatigue life expenditure. An argument for on-line analysis of system disturbance induced torsional stresses is provided.
Keywords :
Control systems; EMTP; Fatigue; Joining processes; Manufacturing; Protection; Rain; Resonance; Shafts; Stress;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1980.319835
Filename :
4114007
Link To Document :
بازگشت