• DocumentCode
    1188908
  • Title

    Application of Synthetic Auto-Reclosing Circuit for Testing High-Voltage Circuit-Breakers

  • Author

    Manganaro, S. ; Schramm, H.H.

  • Author_Institution
    CESI
  • Issue
    6
  • fYear
    1980
  • Firstpage
    2223
  • Lastpage
    2231
  • Abstract
    A synthetic test circuit has been developed to test high-voltage circuit-breakers with respect to their making and auto-reclosing performance at full voltage and full current. The validity of making tests performed at full parameters or at reduced voltahage is checked. The test circuit is applied upon a 420 kV SF6 puffer type circuit-breaker with two breaks per phase. Testing this circuit-breaker can be considered of special interest; particular attention has to be paid to its pre-arcing conditions as due to its high no minal voltage per break.
  • Keywords
    Circuit faults; Circuit stability; Circuit testing; Interrupters; Laboratories; Performance evaluation; Power generation economics; Sulfur hexafluoride; System testing; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1980.319852
  • Filename