DocumentCode :
1190147
Title :
Ground-Fault Protection of Electrical Systems with Emergency or Standby Power
Author :
Castenschiold, Rene
Author_Institution :
Automatic Switch Company, Florham Park, NJ 07932.
Issue :
6
fYear :
1977
Firstpage :
517
Lastpage :
523
Abstract :
Providing reliable ground-fault protection in electrical systems having alternate emergency or standby power can present serious problems unless adequate equipment is selected and properly coordinated. Multiple neutral-to-ground connections may prevent adequate sensing of ground-fault currents and may also cause nuisance tripping of circuit breakers. This paper discusses various approaches that have been proposed to solve these problems. Particular emphasis is placed on code requirements and overall reliability of the electrical systems.
Keywords :
Circuit faults; Conductors; Engines; Grounding; Industrial power systems; National electric code; Power generation; Power system protection; Power system reliability; Switches;
fLanguage :
English
Journal_Title :
Industry Applications, IEEE Transactions on
Publisher :
ieee