DocumentCode :
1191694
Title :
Charging Current Data for Guesswork-Free Design of High-Resistance Grounded Systems
Author :
Baker, David S.
Author_Institution :
Central Engineering Division, Brown & Root, Inc., Houston, TX 77001.
Issue :
2
fYear :
1979
fDate :
3/1/1979 12:00:00 AM
Firstpage :
136
Lastpage :
140
Abstract :
The design of high-resistance grounded power systems requires the sizing of the grounding resistor to provide a current flow equal to or greater than three times the system charging current (Ico) of each phase. In industrial power systems the insulated power cables are a major source of system charging current which flows into line-to-ground faults. Data are presented which will allow cable charging currents to be quickly and precisely determined after the cable size, voltage, footage, insulation type, and thickness have been determined. Charging current data for transformers, motors, generators, and capacitors are also included.
Keywords :
Cable insulation; Cable shielding; Circuit faults; Communication cables; Grounding; Industrial power systems; Power cables; Power transformer insulation; Resistors; Voltage;
fLanguage :
English
Journal_Title :
Industry Applications, IEEE Transactions on
Publisher :
ieee
ISSN :
0093-9994
Type :
jour
DOI :
10.1109/TIA.1979.4503628
Filename :
4503628
Link To Document :
بازگشت