• DocumentCode
    1192527
  • Title

    Short-Circuit Testing of Combination Starters with Inverse-Time Characteristics to UL High Available Fault Standards

  • Author

    Wright, Leland D.

  • Author_Institution
    General Purpose Control Department, General Electric Company, Bloomington, IL 61701.
  • Issue
    6
  • fYear
    1979
  • Firstpage
    630
  • Lastpage
    633
  • Abstract
    Short circuit tests at 18, 25, and 65000 A on combination motor starters with circuit breaker protection are discussed. The appropriate failure criteria from Underwriters´ Laboratories (UL) high available fault standards are referenced. The specialized test equipment required to do these tests are mentioned. Characteristics of the combination starters are described as they relate to short-circuit performance. Finally, the portion of short-circuit energy dissipated in the current arc, arc chutes, circuit elements, contacts, heating of the air, and pressure in the enclosure are measured or calculated where possible.
  • Keywords
    Circuit breakers; Circuit faults; Circuit testing; Current measurement; Energy measurement; Heating; Laboratories; Pressure measurement; Protection; Test equipment;
  • fLanguage
    English
  • Journal_Title
    Industry Applications, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0093-9994
  • Type

    jour

  • DOI
    10.1109/TIA.1979.4503722
  • Filename