DocumentCode :
1192754
Title :
Analysis of Steady-State Transients in Distributed Low-Voltage Power Systems with Rectified Loads
Author :
Gibbons, William P.
Author_Institution :
United States Air Force, Directorate of Civil Engineering, Aeronautical Systems Division, Wright-Patterson Air Force Base, OH 45433.
Issue :
1
fYear :
1980
Firstpage :
51
Lastpage :
59
Abstract :
An analysis of a large number of randomly connected small low-voltage rectifiers to general purpose distribution systems is presented. The primary interest is on single-phase rectifiers connected to 120/208 V three-phase four wire ``wye´´ systems, and shows that the cumulative effect of several different types of rectifiers can produce results which are generally not anticipated. Some of the unanticipated results are overcurrent conditions on the neutral conductor and line conditioning devices which produce effects quite different from those which they are intended to prevent.
Keywords :
Conductors; Microprocessors; Power generation; Power supplies; Power system analysis computing; Power system transients; Rectifiers; Steady-state; Transient analysis; Voltage;
fLanguage :
English
Journal_Title :
Industry Applications, IEEE Transactions on
Publisher :
ieee
ISSN :
0093-9994
Type :
jour
DOI :
10.1109/TIA.1980.4503747
Filename :
4503747