• DocumentCode
    1193422
  • Title

    Use of a Sampling Scheme to Detect Transient Saturation in Protective Current Transformers

  • Author

    Evans, F.J. ; Wells, G.

  • Volume
    19
  • Issue
    3
  • fYear
    1970
  • Firstpage
    144
  • Lastpage
    147
  • Abstract
    Current-transformer (CT) saturation due to primary dc transient offsets presents a problem with regard to fast and predictable operation of protective relays. In this paper, a method is devised and tested for detecting the presence of saturation by sampling the output of the current transformer every millisecond. Successive sampled values are compared and a large difference between these values is used to indicate that saturation has occurred. Results are given that show the circuit operation when actually connected to a CT that is subjected to a transient primary current. Finally, some possible applications of the saturation detector in protection and other areas are suggested.
  • Keywords
    Circuit faults; Current transformers; Fault currents; Iron; Protection; Protective relaying; Sampling methods; Steady-state; Transformer cores; Voltage;
  • fLanguage
    English
  • Journal_Title
    Instrumentation and Measurement, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9456
  • Type

    jour

  • DOI
    10.1109/TIM.1970.4313884
  • Filename