DocumentCode :
1193830
Title :
Electric Cable Installations in Raceways
Author :
Kommers, Thomas A.
Author_Institution :
Okonite Company, 501 Forbes Blvd., South San Francisco, CA 94080.
Issue :
6
fYear :
1980
Firstpage :
787
Lastpage :
796
Abstract :
Installations of extruded insulated conductors in conduits and cable trays are examined. Recommended allowable pulling tensions and sidewall pressures as well as minimum allowable bending radii are defined. Equations for calculating pulling tensions and sidewall pressures are given, taking into account the weight-correction factor. A graphical method for the general solution of weight-correction factors, sidewall pressures, and pulling tensions, is described and illustrated. Proper design of raceway systems and recommended procedures for cable installations are discussed. An example of calculation for the installation of cable in a tray is included.
Keywords :
Aluminum; Cable insulation; Cable shielding; Conductors; Copper; Equations; Eyes; Fasteners; Foot; Pulp and paper industry;
fLanguage :
English
Journal_Title :
Industry Applications, IEEE Transactions on
Publisher :
ieee
ISSN :
0093-9994
Type :
jour
DOI :
10.1109/TIA.1980.4503873
Filename :
4503873
Link To Document :
بازگشت