• DocumentCode
    1195695
  • Title

    Weak Chain Link Breakdown Phenomena of Multigrade Insulation Materials

  • Author

    Gallagher, John M. ; McClung, L.Bruce

  • Author_Institution
    Union Carbide Canada, Ltd., Sarnia, ON, Canada.
  • Issue
    4
  • fYear
    1982
  • fDate
    7/1/1982 12:00:00 AM
  • Firstpage
    348
  • Lastpage
    353
  • Abstract
    Several failures of multigrade insulation systems have been experienced in metal clad, metal enclosed switchgear, and miniature isolated phase busduct systems. The failure sequence of the series insulation system appeared to originate from a point farthest away from the ground plane and not from the insulation in contact with the ground plane. However, in actuality, the ground plane was periodically elevated in relationship to the insulated busbar due to the presence of moisture created by load and ambient temperature cycling and adverse weather conditions. The insulation material in contact with the ground plane, being a high quality track resistant material, did not exhibit permanent deterioration. However the weakest insulation material degraded with time, weakening the overall insulation path to a point that an elevated ground plane condition resulted in failures of the series insulation system. The phenomena experienced in a specific application and the alternatives considered to correct the situation are described.
  • Keywords
    Aluminum; Building materials; Chemicals; Dielectrics and electrical insulation; Electric breakdown; Glass; Insulation life; Lakes; Modems; Plastic insulation;
  • fLanguage
    English
  • Journal_Title
    Industry Applications, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0093-9994
  • Type

    jour

  • DOI
    10.1109/TIA.1982.4504092
  • Filename
    4504092