DocumentCode
1195695
Title
Weak Chain Link Breakdown Phenomena of Multigrade Insulation Materials
Author
Gallagher, John M. ; McClung, L.Bruce
Author_Institution
Union Carbide Canada, Ltd., Sarnia, ON, Canada.
Issue
4
fYear
1982
fDate
7/1/1982 12:00:00 AM
Firstpage
348
Lastpage
353
Abstract
Several failures of multigrade insulation systems have been experienced in metal clad, metal enclosed switchgear, and miniature isolated phase busduct systems. The failure sequence of the series insulation system appeared to originate from a point farthest away from the ground plane and not from the insulation in contact with the ground plane. However, in actuality, the ground plane was periodically elevated in relationship to the insulated busbar due to the presence of moisture created by load and ambient temperature cycling and adverse weather conditions. The insulation material in contact with the ground plane, being a high quality track resistant material, did not exhibit permanent deterioration. However the weakest insulation material degraded with time, weakening the overall insulation path to a point that an elevated ground plane condition resulted in failures of the series insulation system. The phenomena experienced in a specific application and the alternatives considered to correct the situation are described.
Keywords
Aluminum; Building materials; Chemicals; Dielectrics and electrical insulation; Electric breakdown; Glass; Insulation life; Lakes; Modems; Plastic insulation;
fLanguage
English
Journal_Title
Industry Applications, IEEE Transactions on
Publisher
ieee
ISSN
0093-9994
Type
jour
DOI
10.1109/TIA.1982.4504092
Filename
4504092