  • Abstract
    When a high-impedance fault (HIF) occurs in any zone of a distribution system, it is very difficult to detect the fault because the fault current is very small and the time of its occurrence cannot be ascertained. This paper proposes a self-isolation method for an HIF zone in which the feeder remote terminal unit (FRTU) experiencing nil-voltage can identify and isolate autonomously an HIF zone by exchanging voltage and current information with the neighbor FRTUs on the feeder when an HIF occurs under the network-based distribution system. Also, the method was devised to enhance the reliability of HIF identification from the voltage sensor error. Furthermore, new and simple heuristics are proposed, which are required to classify the nil-voltage due to an HIF with nil-voltage caused by general fault outage, scheduled outage, and outage due to the reclosing operation of a protective device (circuit breaker or recloser).
  • Keywords
    fault currents; power distribution faults; fault current; feeder remote terminal unit; high-impedance fault zone; network-based distribution system; self-isolation method; voltage sensor error; Distribution automation system (DAS); distribution system; feeder remote terminal unit (FRTU); high impedance fault (HIF); network-based system; self-identification; self-isolation;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2009.2014482
  • Filename
    4802017