• DocumentCode
    1197597
  • Title

    Field Testing of Voltage Transients Associated with Vacuum Breaker No-Load Switching of a Power Transformer in an Industrial Plant

  • Author

    Ananian, Lucas G. ; Miller, Keith W. ; Titus, Charles H. ; Walsh, George W.

  • Author_Institution
    General Motors Plant Engineering Programs, General Motors
  • Issue
    6
  • fYear
    1983
  • Firstpage
    914
  • Lastpage
    919
  • Abstract
    Reported here are the results of a field investigation of switching-produced transients associated with vacuum circuit breaker switching of an unloaded low-voltage substation transformer. A sufficient sampling of data has been obtained and documented to provide a good statistical basis for this important mode of switching in a very prevalent application area. The results of this field measurements program confirm that the transient voltage environment created by such switching is within, by a wide margin, the expected transient capabilities of the associated power distribution equipment¿specific evaluation being made with respect to the switched transformer.
  • Keywords
    Circuit breakers; Circuit testing; Distortion measurement; Industrial plants; Power measurement; Power system transients; Power transformers; Substations; Switching circuits; System testing;