Abstract :
Single-phase adaptive reclosure (SPAR) schemes applied to transmission lines have been an effective method to improve the stability of power system. Attractive techniques have been proposed for SPAR schemes based on the tripped fault-phase voltage. But for transmission lines with shunt reactors, the voltage is so minor that the error of voltage transformer limits the applications of voltage-based SPAR schemes. To overcome this disadvantage, a new scheme using differential current between the calculated current based on transient fault model and the actual measured current from the fault phase of shunt reactor is proposed in this paper. The calculated current is obtained by using the transient fault model whether there is a transient or permanent fault. In the case of transient fault, the calculated current is close to the measured current due to the actual fault model being close to the calculated model. As for the permanent fault, the calculated current is quite different from the measured current. Therefore, the differential current of the fault phase can be employed to distinguish permanent fault from transient fault. At last, the Alternative Transients Program simulation results show that the developed algorithm can identify the permanent fault correctly and reliably, and is promised to be applied to SPAR for transmission lines with shunt reactors.
Keywords :
power system faults; power system protection; power system relaying; power system transient stability; power transmission protection; Alternative Transients Program simulation; differential current; power system stability; shunt reactors; single phase adaptive reclosure scheme; transient fault model; transmission lines; tripped fault phase voltage; Differential current; relaying protection; shunt reactors; single-phase adaptive reclosure;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2009.2014475
Filename :
4803722
Link To Document :
بازگشت