Abstract :
In previous literature, constant RLC loads were assumed to impose, on the islanding detection method, the hardest detectable case. For this reason, distributed-generation (DG) islanding studies are usually analyzed and performed by using constant RLC loads. In this paper, different types of loads are taken into account by modeling the load´s voltage and frequency dependence. The performance of the over/undervoltage and over/underfrequency protection (OVP/UVP and OFP/UFP) method is examined for the different load models and the results are compared with the constant RLC load case. The analysis is conducted on a constant power-controlled DG designed to operate at unity power factor. A generalized formula, for calculating the nondetection zone of the OVP/UVP and OFP/UFP method, is derived in terms of the load´s voltage and frequency dependence parameters. The analysis is further extended on a constant current-controlled DG interface.
Keywords :
distributed power generation; inverters; overvoltage protection; power factor; distributed-generation islanding; frequency dependent load; inverter; islanding detection method; overfrequency protection method; overvoltage protection; underfrequency protection method; undervoltage protection; unity power factor; Distributed generation (DG); inverter; islanding; over/underfrequency; over/undervoltage; static load models;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2008.2002959
Filename :
4803728
Link To Document :
بازگشت