High-Resistance Grounding and Selective Ground Fault Protection for a Major Industrial Facility
Author
Wang, Gary N. ; Moffatt, William M. ; Vegh, Leslie J. ; Veicht, Frank J.
Author_Institution
Cable Systems Division, Pirelli Cable Corporation
Issue
4
fYear
1984
fDate
7/1/1984 12:00:00 AM
Firstpage
978
Lastpage
985
Abstract
The high-resistance grounded system offers the distinct advantage of service continuity under single ground fault conditions which is critical to many industries such as petroleum, chemical, mining, textile, cement, pulp and paper, food, glass, utility, etc. A new major phosphate mine, with a total of 120 MVA electrical demand capacity, utilizes the high-resistance grounding method for the 480-V and 4160-V distribution systems. A complete ground fault protection scheme that includes both first fault alarm and second fault selective tripping protection was developed for the proper protection of the system. The design of this ground fault protection system has many unique features due to the complexity of the project. Design considerations including the system leakage current, the limitation of transient overvoltage, the grounding methods, the fault detection and annunciation, and selective isolation of faults based on circuit priorities, are analyzed.
Keywords
Cement industry; Chemical industry; Circuit faults; Food industry; Glass industry; Grounding; Industrial plants; Mining industry; Petroleum industry; Protection;
fLanguage
English
Journal_Title
Industry Applications, IEEE Transactions on
Publisher
ieee
ISSN
0093-9994
Type
jour
DOI
10.1109/TIA.1984.4504515
Filename
4504515
Link To Document