DocumentCode
1199810
Title
1976 Installation Problems and Testing of Cable-5 to 35 kV
Author
Lee, Ralph H.
Author_Institution
FELLOW, IEEE
Issue
4
fYear
1984
fDate
7/1/1984 12:00:00 AM
Firstpage
1097
Lastpage
1097
Abstract
Wire and cable, the most ubiquitous of all electrical components, are susceptible to failure from many causes unrelated to service life. Installation damage ranks high in the list of failure causes: the interrelationship between the eight major installation methods and the ways in which they are most likely to cause damage are explained. Damage is largely due to oversharp bending, excessive lateral (sidewall) pressure, puncture, and abrasion. This damage may be avoided by readily usable variations in the installation process, which are outlined in the paper. To detect approaching failure of cable insulation due to damage, defects, or simple electrical degradation, testing with high potential dc at logical intervals has been found highly effective. In- service failures are thus substantially avoided. The reasoning behind testing methods, details on testing procedures, evaluation of results, and testing history are explained.
Keywords
Cable insulation; Circuit testing; Control systems; Degradation; History; Insulation testing; Life testing; Logic testing; Manufacturing; Power cables;
fLanguage
English
Journal_Title
Industry Applications, IEEE Transactions on
Publisher
ieee
ISSN
0093-9994
Type
jour
DOI
10.1109/TIA.1984.4504562
Filename
4504562
Link To Document