Abstract :
A novel scheme for error current compensation of current transformers (CTs) is presented. The method is to apply Hall current transducers (HCTs) based on magnetic force balance to detect and compensate the error current so as to eliminate the error of CT caused by its exciting current. Theoretical analysis and experimental tests clearly illustrate the performance of the proposed scheme. After compensation, the accuracy of the common CT is increased 500 times from 0.5% (5000 ppm) to 0.001% (10 ppm) at the condition of burden Z/sub b/=1 /spl Omega/, cos /spl phi/=1. A self-calibrating method is adopted for a current transformer with the wind ratio of 1:1.
Keywords :
Hall effect; Hall effect transducers; current transformers; error compensation; magnetic forces; Hall current transducer; Hall-effect-based high accuracy current transformer; error current compensation; magnetic force balance; Current transformers; Hall effect; Magnetic analysis; Magnetic cores; Magnetic forces; Magnetic materials; Performance analysis; Power system harmonics; Transducers; Voltage; Current compensation; Hall effect; current transformer (CT);
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2004.837820
Filename :
1375070
Link To Document :
بازگشت