DocumentCode :
1200582
Title :
Evaluation of line voltage drop in presence of unbalance, harmonics, and interharmonics: Theory and applications
Author :
Leva, S. ; Morando, A.P. ; Zaninelli, D.
Author_Institution :
Electr. Eng. Dept., Politecnico di Milano, Italy
Volume :
20
Issue :
1
fYear :
2005
Firstpage :
390
Lastpage :
396
Abstract :
This paper deals with the line voltage drop calculation in presence of disturbances in the electric network, like unbalance, harmonic, and interharmonic components. The Park approach permits to define a calculation expression with a structure very close to the classical one typically employed in case of balanced systems and also permits to underline the role of the imaginary power that quantifies in one term only the effects of disturbances on the voltage drop. In order to text the effectiveness of the proposed methodology, two applications on real industrial plants are presented in the second part of the paper. The comparison with the classical theory and calculation made by using commercial software gives rise to interesting comments and discussion on the proposed approach.
Keywords :
power engineering computing; power supply quality; power system faults; power system harmonics; Park approach; electric network disturbance; interharmonic; line voltage drop evaluation; Differential equations; Industrial plants; Intelligent networks; Power system analysis computing; Power system control; Power system harmonics; Power system modeling; Power system stability; Power systems; Voltage; Harmonics; interharmonics; park transformation; unbalance; voltage drop; zero-sequence components;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2004.837830
Filename :
1375119
Link To Document :