• DocumentCode
    1200582
  • Title

    Evaluation of line voltage drop in presence of unbalance, harmonics, and interharmonics: Theory and applications

  • Author

    Leva, S. ; Morando, A.P. ; Zaninelli, D.

  • Author_Institution
    Electr. Eng. Dept., Politecnico di Milano, Italy
  • Volume
    20
  • Issue
    1
  • fYear
    2005
  • Firstpage
    390
  • Lastpage
    396
  • Abstract
    This paper deals with the line voltage drop calculation in presence of disturbances in the electric network, like unbalance, harmonic, and interharmonic components. The Park approach permits to define a calculation expression with a structure very close to the classical one typically employed in case of balanced systems and also permits to underline the role of the imaginary power that quantifies in one term only the effects of disturbances on the voltage drop. In order to text the effectiveness of the proposed methodology, two applications on real industrial plants are presented in the second part of the paper. The comparison with the classical theory and calculation made by using commercial software gives rise to interesting comments and discussion on the proposed approach.
  • Keywords
    power engineering computing; power supply quality; power system faults; power system harmonics; Park approach; electric network disturbance; interharmonic; line voltage drop evaluation; Differential equations; Industrial plants; Intelligent networks; Power system analysis computing; Power system control; Power system harmonics; Power system modeling; Power system stability; Power systems; Voltage; Harmonics; interharmonics; park transformation; unbalance; voltage drop; zero-sequence components;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2004.837830
  • Filename
    1375119