Title :
A field experiment on power line stabilization by a SMES system
Author :
Irie, F. ; Takeo, M. ; Sato, S. ; Katahira, O. ; Fukui, F. ; Okada, H. ; Ezaki, T. ; Ogawa, K. ; Koba, H. ; Takamatsu, M. ; Shimojo, T.
Author_Institution :
Kinki Univ., Iizuka, Japan
fDate :
1/1/1992 12:00:00 AM
Abstract :
Field experiments on stabilization of a hydro power plant by a SMES (superconducting magnetic energy storage) system are reported, where a generator having a rating of 60 kW at 3.3 kV is connected to a 6.6 kV power distribution line. The SMES system is composed of two 30 kVA GTO (gate turn off) converters and a superconducting magnet system with an energy of 30 kJ at 100 A. Experiments on stabilization for the generator fluctuation caused by a sudden insertion of inductors in the line were successfully performed for some control modes. The value of the SMES system to compensate for a short-period voltage dip is also confirmed
Keywords :
hydroelectric power stations; power cables; stability; superconducting magnet energy storage; 3.3 kV; 30 kJ; 30 kVA; 6.6 kV; 60 kW; GTO converters; SMES system; control modes; field experiment; generator; hydro power plant; power line stabilization; short-period voltage dip; superconducting magnet system; superconducting magnetic energy storage; Converters; Electric variables control; Grounding; Impedance; Inductors; Power distribution lines; Power generation; Power system transients; Samarium; Voltage fluctuations;
Journal_Title :
Magnetics, IEEE Transactions on