DocumentCode
1201666
Title
Failure Analysis of Components Due to 480-V Ground Faults
Author
Love, Daniel J. ; Hashemi, Nasrollah
Author_Institution
Bechtel Power Corporation, P.O. Box 60860, Terminal Annex, Los Angeles, CA 90060.
Issue
4
fYear
1986
fDate
7/1/1986 12:00:00 AM
Firstpage
617
Lastpage
622
Abstract
While many preferred methods exist for protecting components against damage from ground fault currents on 480-V systems, few analyses (if any) have been made concerning the effects on components (molded-case breaker, overload relay, etc.) due to a failure or absence of a ground fault protective device to clear a ground fault. Unlike fuses, which by definition could be considered self-protecting, no such feature exists in relays, molded-case breakers, or overload relay heater elements. The need for sensitive ground fault protection is clarified as by using known I2t techniques to examine the circuit components.
Keywords
Circuit faults; Current transformers; Failure analysis; Fault currents; Fuses; Grounding; Power system protection; Power system relaying; Power transformer insulation; Protective relaying;
fLanguage
English
Journal_Title
Industry Applications, IEEE Transactions on
Publisher
ieee
ISSN
0093-9994
Type
jour
DOI
10.1109/TIA.1986.4504771
Filename
4504771
Link To Document