• DocumentCode
    1202346
  • Title

    Are Cable Shields Being Damaged During Ground Faults?

  • Author

    Hamer, PAUL S. ; Wood, Barry M.

  • Author_Institution
    Chevron Corporation, P. O. Box 5045, San Ramon, CA 94583.
  • Issue
    6
  • fYear
    1986
  • Firstpage
    1149
  • Lastpage
    1155
  • Abstract
    Simulated ground-fault tests (50-700 A) of various cable, ground wire, and conduit configurations are made to determine the proportion of the total ground-fault current carried by the cable metallic shield. The percentage of the total fault current for the various return paths is tabulated, along with representative zero-sequence circuit impedances. General guidelines for protecting cable shields from damage are presented.
  • Keywords
    Cable shielding; Circuit faults; Conductors; Fault currents; Guidelines; Impedance; Power cables; Protection; Proximity effect; Wire;
  • fLanguage
    English
  • Journal_Title
    Industry Applications, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0093-9994
  • Type

    jour

  • DOI
    10.1109/TIA.1986.4504847
  • Filename
    4504847