Are Cable Shields Being Damaged During Ground Faults?
Author
Hamer, PAUL S. ; Wood, Barry M.
Author_Institution
Chevron Corporation, P. O. Box 5045, San Ramon, CA 94583.
Issue
6
fYear
1986
Firstpage
1149
Lastpage
1155
Abstract
Simulated ground-fault tests (50-700 A) of various cable, ground wire, and conduit configurations are made to determine the proportion of the total ground-fault current carried by the cable metallic shield. The percentage of the total fault current for the various return paths is tabulated, along with representative zero-sequence circuit impedances. General guidelines for protecting cable shields from damage are presented.
Keywords
Cable shielding; Circuit faults; Conductors; Fault currents; Guidelines; Impedance; Power cables; Protection; Proximity effect; Wire;