Abstract
The reliable performance of connectors is essential to the operation of an electric utility transmission and distribution system. Since 1962, this performance has been measured using a 500-cycle current cycle test for Class A connectors. An accelerated performance test for connectors has been developed which provides similar results in only 50 cycles. Rather than allowing the conductors to cool slowly, they are submerged in a chilled water bath. This current cycle submersion test offers significant savings in both time and energy
Keywords
electric connectors; life testing; power systems; reliability; Class A connectors; accelerated performance test; cooling; current cycle submersion test; distribution system; electric utility transmission; electrical connectors; life testing; reliability; water bath; ANSI standards; Conductors; Connectors; Equalizers; Laboratories; Life estimation; Manufacturing; Standards development; Temperature control; Testing;