• DocumentCode
    1203599
  • Title

    Corona Inception and Breakdown in Nonuniform Field with Insulating Support in Air

  • Author

    Maller, V.Navinchandra ; Srivastava, Krishan D.

  • Author_Institution
    R&D Centre, Jyoti Limited, P. O. Chemical Industries, Vadodara 390 003 India.
  • Issue
    5
  • fYear
    1987
  • Firstpage
    820
  • Lastpage
    824
  • Abstract
    Corona inception and breakdown was investigated in air for point-to-plane gaps with cylindrical spacers under 60-Hz ac voltages. The effect of a series gap, between the high-voltage point electrode and the spacer, on corona inception and breakdown voltages was also studied. For epoxy spacers the corona inception voltage decreased but the breakdown voltage increased, compared to an equivalent point-to-plane air gap without a spacer. The corona inception voltage characteristic was found to exhibit a maximum at a certain value of the series air gap. The results are interpreted in terms of recently reported observations of spacer surface charging in air and in other insulating gases and insulating barriers.
  • Keywords
    Air gaps; Breakdown voltage; Conductors; Corona; Dielectrics and electrical insulation; Electric breakdown; Electrodes; Gas insulation; Surface charging; Surface discharges;
  • fLanguage
    English
  • Journal_Title
    Industry Applications, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0093-9994
  • Type

    jour

  • DOI
    10.1109/TIA.1987.4504989
  • Filename
    4504989