• DocumentCode
    1204793
  • Title

    Power quality concerns and solutions

  • Author

    Ellis, Robert ; Guidry, Bob

  • Author_Institution
    Rockwell Autom., Cambridge, Ont., Canada
  • Volume
    11
  • Issue
    6
  • fYear
    2005
  • Firstpage
    20
  • Lastpage
    24
  • Abstract
    The pipeline project discussed in this article involved building a new 70-m, 24-in diameter section of a petroleum products pipeline stretch and investigates power issues on a 2,500-hp pipeline booster station adjustable frequency drive. AFDs were originally intended only to be for soft starting, not for continuous use. The active front-end topology uses PWM switching of the rectifier, as well as a reactor/capacitor on the input, to limit harmonics being generated back in to power system.
  • Keywords
    PWM invertors; harmonics suppression; petroleum; pipelines; power conversion harmonics; power supply quality; rectifying circuits; PWM switching; adjustable frequency drive; booster station; capacitor; current source inverter; harmonics; petroleum products; pipeline project; power quality; power system; pulse width modulation; reactor; rectifier; Drives; Frequency; Inductors; Petroleum; Pipelines; Power quality; Power system harmonics; Pulse width modulation; Rectifiers; Topology;
  • fLanguage
    English
  • Journal_Title
    Industry Applications Magazine, IEEE
  • Publisher
    ieee
  • ISSN
    1077-2618
  • Type

    jour

  • DOI
    10.1109/MIA.2005.1524732
  • Filename
    1524732