DocumentCode :
1206797
Title :
Novel Identification Method of Stator Single Phase-to-Ground Fault for Cable-Wound Generators
Author :
Gao, Yan ; Lin, Xiangning ; Tian, Qing ; Liu, Pei
Author_Institution :
Univ. of Sci. & Technol., Wuhan
Volume :
23
Issue :
2
fYear :
2008
fDate :
6/1/2008 12:00:00 AM
Firstpage :
349
Lastpage :
357
Abstract :
A new criterion to detect the stator single phase-to-ground fault for Powerformer is proposed in this paper, which is based on the direction of zero-sequence compositive power flow. By virtue of the analysis of new fault characteristics of Powerformer and the comparison with conventional methods, a novel identification scheme is put forward. The proposed approach detects the ground fault by analyzing the power direction. Only zero-sequence current from the terminal of Powerformer and zero-sequence voltage from the busbar are used in this scheme. Combined with third-harmonic principle, it can provide a 100% coverage of fault detection for the stator windings of Powerformer. The effectiveness of this scheme is validated with the Matlab simulation results.
Keywords :
electric generators; electrical faults; fault diagnosis; stators; cable-wound generators; fault detection; powerformer; stator single phase-to-ground fault; stator windings; third- harmonic principle; zero-sequence compositive power flow; zero-sequence current; Fault currents; Fault detection; Fault diagnosis; Frequency; Load flow; Phase detection; Power generation; Relays; Stator windings; Voltage control; Fault components; Powerformer; stator single phase-to-ground fault; zero-sequence compositive power flow;
fLanguage :
English
Journal_Title :
Energy Conversion, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8969
Type :
jour
DOI :
10.1109/TEC.2008.921554
Filename :
4505389
Link To Document :
بازگشت