  • Abstract
    The actual stator bars of an 18 kV/300 MW generator were used for accelerated multistress aging tests to investigate the degradation of ground insulation. An aging system with combined stresses including thermal, electrical, mechanical vibration, and thermomechanical factors was used to test the aging of stator bar specimens. The nondestructive parameters including partial discharge (PD) quantities and dissipation factor parameters were measured during aging test in order to evaluate the degradation of stator ground wall insulation. At the end of the aging test, an AC breakdown test was performed on the bars in order to obtain the remaining breakdown voltage (BDV) after their nondestructive data had been measured. The changes of nondestructive parameters indicated that the degradation of ground wall insulation. For example, the changes of skewness of indicated the shape of voids in ground insulation changes from flat to narrow, and even exhibits treeing, which is dangerous to insulation because it shortens the effective distance of insulation between high voltage and the ground. The results obtained are summarized as follows. The BDV data fit a Weibull distribution. The correlation between the dissipation factor, the PD parameters, and the breakdown voltage were analyzed, among which the skewness of the average discharge had the most correlation with breakdown voltage.
  • Keywords
    Weibull distribution; ageing; electric breakdown; electric generators; machine insulation; AC breakdown test; BDV; Weibull distribution; breakdown voltage; dissipation factor; dissipation factor parameters; generator stator ground wall insulation; multistresses aging; nondestructive parameters; Accelerated aging; Insulation testing; Life estimation; Nondestructive testing; Partial discharges; Stator bars; Thermal degradation; Thermal factors; Thermal stresses; Vibrations; Aging; breakdown voltage (BDV); correlation; discharge; dissipation factor; generator; ground wall insulation; multi-stress; nondestructive; partial discharge (PD) quantity;
  • fLanguage
    English
  • Journal_Title
    Energy Conversion, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8969
  • Type

    jour

  • DOI
    10.1109/TEC.2008.918653
  • Filename
    4505392