DocumentCode
1207376
Title
Partial discharge. IX. PD in gas-insulated substations-fundamental considerations
Author
Baumgartner, R. ; Fruth, B. ; Lanz, W. ; Pettersson, K.
Author_Institution
ABB Switzerland, Zurich, Switzerland
Volume
7
Issue
6
fYear
1991
Firstpage
5
Lastpage
13
Abstract
For pt.VIII see ibid., vol.7, no.5, p.9 et seq. (1991). The physical aspects of partial discharge (PD) in SF/sub 6/ gas-insulated substations (GIS) are reviewed. The orientation is toward present and developing techniques for evaluating defects in solid and gaseous insulation systems on the basis of PD measurement. Standard evaluation methods provide an indication of PD in GIS, but cannot quantitatively determine the type and size of defect. Statistical analysis of PD activity, together with physical models for the various types of discharge and defects, provides the basis for more advanced interpretation. Measurements of PD activity that do not require an absolute calibration are of greatest utility.<>
Keywords
electric breakdown of gases; gaseous insulation; partial discharges; substations; sulphur compounds; GIS; PD activity; SF/sub 6/; gas-insulated substations; gaseous insulation systems; partial discharge; physical models; solid insulation systems; Charge measurement; Current measurement; Geographic Information Systems; Insulation; Partial discharges; Solids; Stress; Substations; Sulfur hexafluoride; Voltage;
fLanguage
English
Journal_Title
Electrical Insulation Magazine, IEEE
Publisher
ieee
ISSN
0883-7554
Type
jour
DOI
10.1109/57.108819
Filename
108819
Link To Document