Title :
An enhanced method of providing sensitive bus fault protection
Author :
Stringer, Norman T.
Author_Institution :
Artwel Electr. Inc., Sacramento, CA, USA
Abstract :
The application of bus fault protection in industrial facilities has been primarily limited to overcurrent relays located at the upstream breaker. This does not always provide the best protection for bus faults. The protection sensitivity is limited because of the need to coordinate with other downstream overcurrent devices. This paper describes an enhanced method of applying sensitive bus fault protection using digital overcurrent relays. In addition, this method provides both downstream feeder breaker backup protection and relay backup protection.
Keywords :
busbars; industrial power systems; overcurrent protection; power system faults; power system protection; power system relaying; relay protection; digital overcurrent relays; downstream feeder breaker backup protection; industrial facilities; overcurrent devices; protection sensitivity; relay backup protection; sensitive bus fault protection method; upstream breaker; Delay effects; Digital relays; Industrial plants; Industrial power systems; Industry Applications Society; Medium voltage; Power system faults; Power system protection; Power system relaying; Protective relaying;
Journal_Title :
Industry Applications, IEEE Transactions on
DOI :
10.1109/TIA.2003.810932