• DocumentCode
    1210053
  • Title

    An enhanced method of providing sensitive bus fault protection

  • Author

    Stringer, Norman T.

  • Author_Institution
    Artwel Electr. Inc., Sacramento, CA, USA
  • Volume
    39
  • Issue
    3
  • fYear
    2003
  • Firstpage
    600
  • Lastpage
    604
  • Abstract
    The application of bus fault protection in industrial facilities has been primarily limited to overcurrent relays located at the upstream breaker. This does not always provide the best protection for bus faults. The protection sensitivity is limited because of the need to coordinate with other downstream overcurrent devices. This paper describes an enhanced method of applying sensitive bus fault protection using digital overcurrent relays. In addition, this method provides both downstream feeder breaker backup protection and relay backup protection.
  • Keywords
    busbars; industrial power systems; overcurrent protection; power system faults; power system protection; power system relaying; relay protection; digital overcurrent relays; downstream feeder breaker backup protection; industrial facilities; overcurrent devices; protection sensitivity; relay backup protection; sensitive bus fault protection method; upstream breaker; Delay effects; Digital relays; Industrial plants; Industrial power systems; Industry Applications Society; Medium voltage; Power system faults; Power system protection; Power system relaying; Protective relaying;
  • fLanguage
    English
  • Journal_Title
    Industry Applications, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0093-9994
  • Type

    jour

  • DOI
    10.1109/TIA.2003.810932
  • Filename
    1201523