• DocumentCode
    1211549
  • Title

    A Real-Time Voltage Instability Identification Algorithm Based on Local Phasor Measurements

  • Author

    Corsi, Sandro ; Taranto, Glauco N.

  • Author_Institution
    CESI Spa., Milan
  • Volume
    23
  • Issue
    3
  • fYear
    2008
  • Firstpage
    1271
  • Lastpage
    1279
  • Abstract
    This paper proposes a new voltage instability risk indicator based on local phasor measurements at fast sampling rate. The effectiveness of the indicator is analyzed at EHV load and ldquotransitrdquo buses. The risk criterion is based on the real-time computation of the Thevenin equivalent impedance of the classic electrical circuit given by an equivalent generator connected to an equivalent load impedance through an equivalent connecting impedance. The main contribution of the paper is the innovating algorithm utilized on the real-time adaptive identification of the Thevenin voltage and impedance equivalents. The algorithm performance is shown through a detailed sensitivity analysis. The paper presents important numerical results from the actual Italian EHV network.
  • Keywords
    electric current measurement; electric impedance; equivalent circuits; power system identification; power system measurement; sensitivity analysis; voltage measurement; EHV load; Italian EHV network; Thevenin equivalent impedance; classic electrical circuit; equivalent generator; fast sampling rate; phasor measurements; real-time adaptive identification; real-time voltage instability identification algorithm; sensitivity analysis; Dynamic simulation; Thevenin equivalent; long-term voltage stability; online VSA; phasor measurement unit (PMU); voltage stability;
  • fLanguage
    English
  • Journal_Title
    Power Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8950
  • Type

    jour

  • DOI
    10.1109/TPWRS.2008.922586
  • Filename
    4512044