DocumentCode
1211893
Title
Review of chemical indicators of degradation of cellulosic electrical paper insulation in oil-filled transformers
Author
Emsley, A.M. ; Stevens, G.C.
Author_Institution
Dept. of Chem., Surrey Univ., Guildford, UK
Volume
141
Issue
5
fYear
1994
fDate
9/1/1994 12:00:00 AM
Firstpage
324
Lastpage
334
Abstract
Chemical and thermal degradation of electrical insulation in oil-filled transformers, mechanisms of failure and methods of condition monitoring and of life prediction are reviewed. An insulation life prediction model is developed and estimates of insulation life are presented under a variety of oil/paper conditions. Systematic measurements of the concentration of chemical indicators in transformer oil are used to demonstrate that furaldehyde and related products can be used to detect high rates of paper degradation. Similarly, phenol and related products indicate electrical degradation in phenol-formaldehyde resins
Keywords
fault location; indicators; insulating oils; insulation testing; paper; power transformers; transformer insulation; cellulosic electrical paper insulation; chemical degradation; chemical indicators; condition monitoring; degradation; electrical degradation; electrical insulation; failure; furaldehyde; insulation life prediction model; life prediction; oil-filled transformers; paper degradation; phenol; phenol-formaldehyde resins; power transformers; thermal degradation;
fLanguage
English
Journal_Title
Science, Measurement and Technology, IEE Proceedings -
Publisher
iet
ISSN
1350-2344
Type
jour
DOI
10.1049/ip-smt:19949957