• DocumentCode
    1211893
  • Title

    Review of chemical indicators of degradation of cellulosic electrical paper insulation in oil-filled transformers

  • Author

    Emsley, A.M. ; Stevens, G.C.

  • Author_Institution
    Dept. of Chem., Surrey Univ., Guildford, UK
  • Volume
    141
  • Issue
    5
  • fYear
    1994
  • fDate
    9/1/1994 12:00:00 AM
  • Firstpage
    324
  • Lastpage
    334
  • Abstract
    Chemical and thermal degradation of electrical insulation in oil-filled transformers, mechanisms of failure and methods of condition monitoring and of life prediction are reviewed. An insulation life prediction model is developed and estimates of insulation life are presented under a variety of oil/paper conditions. Systematic measurements of the concentration of chemical indicators in transformer oil are used to demonstrate that furaldehyde and related products can be used to detect high rates of paper degradation. Similarly, phenol and related products indicate electrical degradation in phenol-formaldehyde resins
  • Keywords
    fault location; indicators; insulating oils; insulation testing; paper; power transformers; transformer insulation; cellulosic electrical paper insulation; chemical degradation; chemical indicators; condition monitoring; degradation; electrical degradation; electrical insulation; failure; furaldehyde; insulation life prediction model; life prediction; oil-filled transformers; paper degradation; phenol; phenol-formaldehyde resins; power transformers; thermal degradation;
  • fLanguage
    English
  • Journal_Title
    Science, Measurement and Technology, IEE Proceedings -
  • Publisher
    iet
  • ISSN
    1350-2344
  • Type

    jour

  • DOI
    10.1049/ip-smt:19949957
  • Filename
    338827