Self-calibratable voltage transformer with part-per-million accuracy
Author_Institution :
Div. of Appl. Phys., CSIRO, Lindfield, NSW, Australia
fDate :
9/1/1994 12:00:00 AM
Abstract :
The design and construction of a 1000 V/100 V, two-stage voltage transformer with burden compensation, which has errors of no more than a few parts per million over its working range of voltage levels and burdens, is described. By dividing the primary winding into ten equal sections and by enclosing the primary and secondary windings in electrostatic screens, it is shown that the transformer can be self-calibrated by a build-up technique, without reference to standard transformers or other potential dividers
Keywords :
calibration; compensation; potential transformers; transformer windings; 100 V; 1000 V; burden compensation; construction; design; electrostatic screens; potential dividers; primary winding; primary windings; secondary windings; selfcalibration; two-stage voltage transformer;
Journal_Title :
Science, Measurement and Technology, IEE Proceedings -
DOI :