DocumentCode :
1211924
Title :
Self-calibratable voltage transformer with part-per-million accuracy
Author :
Betts, P.J.
Author_Institution :
Div. of Appl. Phys., CSIRO, Lindfield, NSW, Australia
Volume :
141
Issue :
5
fYear :
1994
fDate :
9/1/1994 12:00:00 AM
Firstpage :
379
Lastpage :
382
Abstract :
The design and construction of a 1000 V/100 V, two-stage voltage transformer with burden compensation, which has errors of no more than a few parts per million over its working range of voltage levels and burdens, is described. By dividing the primary winding into ten equal sections and by enclosing the primary and secondary windings in electrostatic screens, it is shown that the transformer can be self-calibrated by a build-up technique, without reference to standard transformers or other potential dividers
Keywords :
calibration; compensation; potential transformers; transformer windings; 100 V; 1000 V; burden compensation; construction; design; electrostatic screens; potential dividers; primary winding; primary windings; secondary windings; selfcalibration; two-stage voltage transformer;
fLanguage :
English
Journal_Title :
Science, Measurement and Technology, IEE Proceedings -
Publisher :
iet
ISSN :
1350-2344
Type :
jour
DOI :
10.1049/ip-smt:19941068
Filename :
338830
Link To Document :
بازگشت