DocumentCode :
1213075
Title :
Current disparity in multi-column surge arresters
Author :
Haddad, A. ; Waters, R.T. ; German, D.M. ; Abdul-Malek, Z.
Author_Institution :
High Voltage Group, Cardiff Univ., UK
Volume :
152
Issue :
6
fYear :
2005
Firstpage :
945
Lastpage :
951
Abstract :
High-voltage surge arresters for high-current, high-energy duty often comprise several parallel ZnO columns. The extreme nonlinearity of the voltage-current characteristics of these columns demands close matching. However, even initially well matched columns can be unbalanced by ageing, partial discharges, self inductance and thermal effects. Two test techniques are described to examine current disparity in a pair of parallel 15 kV rated surge arresters: these are a current-ratio method and a current-difference method. The tests allow three aspects of parallel operation to be investigated: the use of ballast resistors to minimise mismatch effects and to increase energy absorption rating; the influence of the arrester layout on current parity; and temperature-difference perturbation of transient characteristics.
Keywords :
ageing; arresters; inductance; overvoltage protection; partial discharges; perturbation techniques; power system protection; power system transients; zinc compounds; 15 kV; ZnO; ZnO columns; ageing; ballast resistors; current disparity; current-difference method; current-ratio method; energy absorption rating; high-voltage surge arresters; multicolumn surge arresters; parallel operation; partial discharges; self inductance; temperature-difference perturbation; thermal effects; transient characteristics; voltage-current characteristics;
fLanguage :
English
Journal_Title :
Generation, Transmission and Distribution, IEE Proceedings-
Publisher :
iet
ISSN :
1350-2360
Type :
jour
DOI :
10.1049/ip-gtd:20045051
Filename :
1532116
Link To Document :
بازگشت