    Mechanical properties of copper in relation to power-transformer design

  • Author

    Corcoran, Robert J. ; Palmer, Selwyn

  • Author_Institution
    Canada Wire & Cable Ltd., Toronto, Canada
  • Volume
    1
  • Issue
    3
  • fYear
    1987
  • fDate
    5/1/1987 12:00:00 AM
  • Firstpage
    154
  • Lastpage
    157
  • Abstract
    Pure soft copper in power-transformer windings may not be strong enough for units of low impedance or high rating. Increased strength may be obtained by alloying or cold working. Cold-worked copper will soften with time and temperature, so it is important to predict the effects of overloads and short circuits. A method of using Arrhenius plots to do this from laboratory measurements is described which shows that, for normal power transformers, conductor softening will not occur in normal service
  • Keywords
    copper; mechanical properties of substances; power transformers; short-circuit currents; transformer windings; Arrhenius plots; Cu mechanical properties; alloying; cold working; conductor softening; low impedance; overloads; power-transformer windings; rating; short circuits;