DocumentCode
1214954
Title
Mechanical properties of copper in relation to power-transformer design
Author
Corcoran, Robert J. ; Palmer, Selwyn
Author_Institution
Canada Wire & Cable Ltd., Toronto, Canada
Volume
1
Issue
3
fYear
1987
fDate
5/1/1987 12:00:00 AM
Firstpage
154
Lastpage
157
Abstract
Pure soft copper in power-transformer windings may not be strong enough for units of low impedance or high rating. Increased strength may be obtained by alloying or cold working. Cold-worked copper will soften with time and temperature, so it is important to predict the effects of overloads and short circuits. A method of using Arrhenius plots to do this from laboratory measurements is described which shows that, for normal power transformers, conductor softening will not occur in normal service
Keywords
copper; mechanical properties of substances; power transformers; short-circuit currents; transformer windings; Arrhenius plots; Cu mechanical properties; alloying; cold working; conductor softening; low impedance; overloads; power-transformer windings; rating; short circuits;
fLanguage
English
Journal_Title
Power Engineering Journal
Publisher
iet
ISSN
0950-3366
Type
jour
DOI
10.1049/pe:19870029
Filename
4807736
Link To Document