Abstract :
The Chateauguay HVDC back-to-back scheme with interconnections to the 765 kV transmission to the USA and to Beauharnois generators can exhibit, under certain operating conditions, second harmonic resonance problems. The author presents a thorough analysis of the problem using an eigenvalue and frequency domain approach. The analysis explains the mechanism of the excitation of the second harmonic instability by the presence of HVDC converters. The influence of changing the control parameters of the static VAr compensator at the Chateauguay terminal is also studied. Finally, an assessment is made of the effectiveness of present countermeasure schemes, namely the auxiliary DC stabilizing controls and the installation of second harmonic filters
Keywords :
DC power transmission; harmonics; power systems; stability; static VAr compensators; 765 kV; Beauharnois generators; Chateauguay HVDC back-to-back scheme; HVDC converters; USA; auxiliary DC stabilizing controls; power systems; second harmonic filters; second harmonic instability; static VAr compensator; Eigenvalues and eigenfunctions; Frequency domain analysis; Gold; HVDC transmission; Harmonic analysis; Power harmonic filters; Power system analysis computing; Power system harmonics; Resonance; Static VAr compensators;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.108935
Filename :
108935
Link To Document :
بازگشت