DocumentCode
1215341
Title
Statistical Property of Breakdown between Electrode and Shield in High-Voltage Vacuum Interrupter
Author
Toya, H. ; Hayashi, T. ; Shinozaki, Y. ; Murai, Y.
Volume
13
Issue
5
fYear
1985
Firstpage
311
Lastpage
314
Abstract
Statistical property of the breakdown between stainless or copper electrode and stainless arc shield is studied by applying (250 à 2000)-¿s switching impulses to model vacuum interrupters. Higher breakdown voltages are obtained in negative polarity than in positive polarity. The effective area of breakdown which takes the electric-field distribution on the anode surface into account is introduced to explain the polarity effect of breakdown voltage using Weibull statistics.