Abstract
The authors discuss corona and breakdown in compressed sulfur hexafluoride (SF6) gas-insulated transmission line (GITL) equipment due to free conducting particles. For particle-contaminated conditions, dynamic models of particle movement and particle-initiated corona and breakdown have been developed. Moreover, a method is proposed to utilize externally measured quantities (for example, time to first corona, corona magnitude, and repetition frequency) during testing and commissioning for identifying the size of contaminating particles
Keywords
corona; electric breakdown of gases; gaseous insulation; insulation testing; sulphur compounds; switchgear; GITL systems; SF6; breakdown; commissioning; corona; dynamic models; free conducting particles; gas-insulated transmission line; particle movement; particle-contaminated conditions; repetition frequency; testing; time to first corona; Corona; Electric breakdown; Frequency measurement; Gas insulated transmission lines; Particle measurements; Pollution measurement; Size measurement; Sulfur hexafluoride; Time measurement; Transmission line measurements;