• DocumentCode
    1219637
  • Title

    Particle-initiated corona and breakdown in GITL systems

  • Author

    Morcos, M.M. ; Anis, H. ; Srivastava, K.D.

  • Author_Institution
    Kansas State Univ., Manhattan, KS, USA
  • Volume
    24
  • Issue
    4
  • fYear
    1989
  • fDate
    8/1/1989 12:00:00 AM
  • Firstpage
    561
  • Lastpage
    571
  • Abstract
    The authors discuss corona and breakdown in compressed sulfur hexafluoride (SF6) gas-insulated transmission line (GITL) equipment due to free conducting particles. For particle-contaminated conditions, dynamic models of particle movement and particle-initiated corona and breakdown have been developed. Moreover, a method is proposed to utilize externally measured quantities (for example, time to first corona, corona magnitude, and repetition frequency) during testing and commissioning for identifying the size of contaminating particles
  • Keywords
    corona; electric breakdown of gases; gaseous insulation; insulation testing; sulphur compounds; switchgear; GITL systems; SF6; breakdown; commissioning; corona; dynamic models; free conducting particles; gas-insulated transmission line; particle movement; particle-contaminated conditions; repetition frequency; testing; time to first corona; Corona; Electric breakdown; Frequency measurement; Gas insulated transmission lines; Particle measurements; Pollution measurement; Size measurement; Sulfur hexafluoride; Time measurement; Transmission line measurements;
  • fLanguage
    English
  • Journal_Title
    Electrical Insulation, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9367
  • Type

    jour

  • DOI
    10.1109/14.34190
  • Filename
    34190