Abstract
Frequency response analysis (FRA) is a widely accepted testing technique to assess the mechanical condition of a power transformer. However, it has been reported that FRA is also sensitive to non-mechanical parameters such as the temperature and moisture content of the insulation. Therefore, further studies are required to investigate the ability of FRA on examining the transformer insulation condition. In this paper a study based on an insulation degradation of a single phase 5 kVA model transformer is presented. Throughout the accelerated insulation degradation process, FRA and Frequency Domain Dielectric Spectroscopy (FDS) measurements are performed to analyze the degradation condition. Two methodologies are proposed to analyze the FRA results based on the relative change of capacitance and change of inter-winding capacitance. Results obtained from these approaches are verified with FDS analysis.
Keywords
ageing; frequency response; moisture; power transformer insulation; spectroscopy; transformer windings; FDS analysis; FDS techniques; FRA; FRA techniques; degradation condition; frequency domain dielectric spectroscopy; frequency response analysis; inter-winding capacitance; moisture content; temperature content; transformer insulation; transformer insulation ageing; Aging; Capacitance; Moisture; Oil insulation; Power transformer insulation; Windings; Power transformers; frequency domain spectroscopy; frequency response analysis; insulation ageing;
fLanguage
English
Journal_Title
Dielectrics and Electrical Insulation, IEEE Transactions on
Publisher
ieee
ISSN
1070-9878
Type
jour
DOI
10.1109/TDEI.2015.7076829
Filename
7076829
Link To Document