DocumentCode :
122611
Title :
Investigation of active power measurements in harmonic conditions
Author :
Kochawat, Tanya ; Phapukdee, Voraphol
Author_Institution :
Electr. Metrol. Dept., Nat. Inst. of Metrol. (Thailand), Pathumthani, Thailand
fYear :
2014
fDate :
19-21 March 2014
Firstpage :
1
Lastpage :
4
Abstract :
An investigation of active power measurements using 4 different accuracy level watt meters when specific harmonic conditions (different harmonic currents, 4 values of fundamental power factor (PF) and no phase shift between harmonic voltages and harmonic currents) in the system was performed. Expected active powers during harmonic environments based on IEEE Std. 1459-2010 were calculated to be reference powers. Results show the reference and working level watt meters provide measured active powers perfectly while the general measuring watt meter gives a large error especially when a harmonic content is high but a PF is very low. Thus, uses of active power values in harmonic conditions obtained from watt meters need to be careful particularly those obtained from general measuring watt meters.
Keywords :
IEEE standards; power factor; power measurement; power system harmonics; wattmeters; IEEE Std. 1459-2010; PF; active power measurements; active power values; harmonic conditions; harmonic currents; harmonic environments; harmonic voltages; power factor; watt meters; Abstracts; Area measurement; Atmospheric measurements; Distortion measurement; Harmonic analysis; Monitoring; Particle measurements; harmonic active power; watt meter;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Engineering Congress (iEECON), 2014 International
Conference_Location :
Chonburi
Type :
conf
DOI :
10.1109/iEECON.2014.6925887
Filename :
6925887
Link To Document :
بازگشت