• DocumentCode
    1227262
  • Title

    Assuring the quality of impulse voltage calibration results issued by a calibration laboratory

  • Author

    Hughes, R.C. ; Lightfoot, Hugh A. ; McComb, Terence R.

  • Author_Institution
    Nat. Grid Co., Leatherhead, UK
  • Volume
    18
  • Issue
    3
  • fYear
    2003
  • fDate
    7/1/2003 12:00:00 AM
  • Firstpage
    701
  • Lastpage
    704
  • Abstract
    This paper describes high voltage impulse measurements made under the controlled conditions of a calibration or national measurement laboratory to establish the best agreement that could be achieved in comparison measurements on small reference dividers. This comparison to establish mutual international traceability between NRC and National Grid has shown that the peak voltage of a smooth lightning impulse was measured by both laboratories to within 0.2% with an estimated uncertainty of ±0.2% at a level of confidence not less than 95%. The authors make recommendations on how calibrations of reference measuring systems should be performed.
  • Keywords
    calibration; high-voltage techniques; laboratories; lightning; pulse measurement; quality control; test facilities; voltage measurement; National Grid; National Research Council; calibration laboratory; high voltage impulse measurements; impulse voltage calibration results quality; international traceability; national measurement laboratory; peak voltage measurement; small reference dividers; smooth lightning impulse; Calibration; Councils; IEC standards; ISO standards; Laboratories; Lightning; Performance evaluation; Pulse measurements; Quality assurance; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2003.813810
  • Filename
    1208344