    Analytical Description of the Load-Loss Asymmetry Phenomenon in Three-Phase Three-Limb Transformers

  • Author

    Escarela-Perez, R. ; Kulkarni, S.V. ; Alvarez-Ramirez, J. ; Kaushik, K.

  • Author_Institution
    Univ. Nac. Autonoma de Mexico, Azcapotzalco
  • Volume
    24
  • Issue
    2
  • fYear
    2009
  • fDate
    4/1/2009 12:00:00 AM
  • Firstpage
    695
  • Lastpage
    702
  • Abstract
    The asymmetry phenomenon observed during the load-loss test of three-phase transformers is rigorously analyzed. The transformer is represented as a three-port impedance network despite its six-port network nature, making any formal study more tractable. The analytical restrictions required for such a representation are derived. As a result, it is possible to mathematically prove (and understand) the asymmetrical behavior of a three-phase transformer subjected to the load-loss test. Only two circuit-field simulations or tests (single-phase load-loss tests) are required to obtain the impedance system of the six-winding transformer. A 3-D finite-element (FE) model of a transformer is used here to obtain its short-circuit impedances, exemplifying the use and extent of the analytical results. The eddy currents generated at the transformer tank and frame are properly taken into consideration. The short-circuit impedance model is validated with the 3-D FE model and with a six-port network approach that has been previously verified.
  • Keywords
    finite element analysis; load flow; transformer windings; 3D finite-element model; load-loss asymmetry phenomenon; six-winding transformer; three-phase three-limb transformers; three-phase transformer; three-port impedance network; Asymmetry phenomenon; finite-element models (FEMs); network models; short-circuit impedances;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2008.923988
  • Filename