Title : 
Wind tunnel studies of transmission line conductor temperatures
         
        
            Author : 
Hall, J.F. ; Deb, Alok Kanti ; Savoullis, J.
         
        
            Author_Institution : 
Pacific Gas & Electric Co., San Ramon, CA, USA
         
        
        
        
        
            fDate : 
4/1/1988 12:00:00 AM
         
        
        
        
            Abstract : 
Transmission line conductor thermal studies conducted in a wind tunnel are reported. AAC and ACSR core-to-surface temperature gradient and conductor steady-state, transient, and step response were measured as a function of wind speed and direction, temperature, and current. Data are presented and compared with two conductor thermal models, the House-Tuttle model and the EPRI DYNAMP model
         
        
            Keywords : 
overhead line conductors; power overhead lines; thermal analysis; wind tunnels; power overhead lines; temperature gradient; thermal analysis; thermal models; transmission line conductor; wind speed; Conductors; Current measurement; Power system transients; Steady-state; Temperature; Thermal conductivity; Transmission line measurements; Transmission lines; Velocity measurement; Wind speed;
         
        
        
            Journal_Title : 
Power Delivery, IEEE Transactions on