DocumentCode
1233604
Title
A Refined Hilbert–Huang Transform With Applications to Interarea Oscillation Monitoring
Author
Laila, Dina Shona ; Messina, Arturo Roman ; Pal, Bikash C.
Author_Institution
Electr. & Electron. Eng. Dept., Imperial Coll. London, London
Volume
24
Issue
2
fYear
2009
fDate
5/1/2009 12:00:00 AM
Firstpage
610
Lastpage
620
Abstract
This paper focuses on the refinement of standard Hilbert-Huang transform (HHT) technique to accurately characterize time varying, multicomponents interarea oscillations. Several improved masking techniques for empirical mode decomposition (EMD) and a local Hilbert transformer are proposed and a number of issues regarding their use and interpretation are identified. Simulated response data from a complex power system model are used to assess the efficacy of the proposed techniques for capturing the temporal evolution of critical system modes. It is shown that the combination of the proposed methods result in superior frequency and temporal resolution than other approaches for analyzing complicated nonstationary oscillations.
Keywords
Hilbert transforms; oscillations; power system transients; critical system modes; empirical mode decomposition; interarea oscillation monitoring; local Hilbert transformer; masking techniques; nonstationary oscillation analysis; power system model; power systems transient response; refined Hilbert-Huang transform; Convolution filter; Hilbert–Huang transform; empirical mode decomposition; interarea oscillation; masking;
fLanguage
English
Journal_Title
Power Systems, IEEE Transactions on
Publisher
ieee
ISSN
0885-8950
Type
jour
DOI
10.1109/TPWRS.2009.2016478
Filename
4813184
Link To Document