DocumentCode :
1234743
Title :
Calculation of self and mutual impedances between sections of transformer windings
Author :
Wilcox, D.J. ; Hurley, W.G. ; Conlon, M.
Author_Institution :
Fac. of Eng., Univ. Coll., Galway, Ireland
Volume :
136
Issue :
5
fYear :
1989
fDate :
9/1/1989 12:00:00 AM
Firstpage :
308
Lastpage :
314
Abstract :
The author shows how a new frequency-dependent impedance formula, derived on the assumption of a solid homogeneous core, may be adapted to permit calculation of the self and mutual impedances of coil sections on a practical transformer core. Experimental measurements, in comparison with calculated values, show that the effects of the laminations can be accurately simulated by using two distinct resistivities in different parts of the basic formula. A method is given for determining these quantities experimentally. Application of the resulting formula in transient analysis automatically accounts for the effects of transient flux penetration into the transformer core, including the effects of frequency-dependent inductances and transient eddy currents in the core laminations
Keywords :
eddy currents; electric impedance; power transformers; transformer windings; core laminations; frequency-dependent impedance formula; mutual impedances; self impedances; transformer windings; transient eddy currents; transient flux penetration;